dry type distribution transformer

SCB18 Cast-Resin Dry-Type Transformer

Product Overview

The SCB18 is a three-phase cast-resin dry-type transformer. The technical schedule below covers ratings from 30 to 2,000 kVA, with 6, 6.3 and 10 kV high-voltage options and a 0.4 kV low-voltage rating. Load losses are listed separately for the B, F and H reference-temperature columns.

Construction and Features

  • Epoxy-resin cast dry-type construction.
  • Mechanical strength, short-circuit withstand capability and low partial discharge are described as series design features.
  • Forced-air cooling is described for additional loading; the permitted loading and duration depend on the selected design and operating conditions.
  • Temperature monitoring and protection systems can be specified.
  • Confirm the enclosure, environmental conditions and installation arrangement for the selected unit.

Technical Parameters

Parameter Technical Data
Listed rated capacities 30–2,000 kVA
Number of phases Three-phase
High-voltage options shown 6 kV, 6.3 kV and 10 kV
Low-voltage rating shown 0.4 kV
Connection groups shown Yyn0 or Dyn11
Insulation system, enclosure and cooling Confirm for the selected configuration

SCB18 Loss Data

Rated Power (kVA) No-load Loss (W) Load Loss: B (100°C), W Load Loss: F (120°C), W Load Loss: H (145°C), W
30 105 605 640 685
50 155 845 900 965
80 210 1160 1240 1330
100 230 1330 1415 1520
125 270 1565 1665 1780
160 310 1800 1915 2050
200 360 2135 2275 2440
250 415 2330 2485 2665
315 510 2945 3125 3355
400 570 3375 3590 3850
500 670 4130 4390 4705
630 775 4975 5290 5660
800 875 5895 6265 6715
1000 1020 6885 7315 7885
1250 1205 8190 8720 9335
1600 1415 9945 10555 11320
2000 1760 12240 18006 14005

The 1,000 kVA entry lists a no-load loss of 1,020 W. Load loss is 6,885 W in the B (100°C) column, 7,315 W in the F (120°C) column and 7,885 W in the H (145°C) column.

Load-loss values are listed at separate reference temperatures. Confirm the insulation system and applicable reference temperature for the selected design before comparing performance or placing an order.

Selection and Enquiries

Send the required rated capacity, primary and secondary voltages, frequency, connection, installation conditions, enclosure requirements, quantity and project location. Request the confirmed dimensions, weight, sound-level data, short-circuit impedance and scope of supply for the selected unit.

Installation and Maintenance

Installation, ventilation, fire-safety provisions and any hazardous-area requirements must be assessed for the selected design and site. Dry-type construction does not by itself establish an explosion-protection rating. Follow the manufacturer’s installation, inspection and maintenance instructions.

Our Product Series

We provide a variety of MV & HV transformers worldwide, compliant with international standards and certifications
UL / cUL / CSA / CE / CESI / ISO / NEMA / FM / IEEE / DOE / EU / BS and more

Dry-type Distribution Transformer
Oil-immersed Distribution Transformer
Transformer Substation
Choose us
Trusted by Industry Leaders Worldwide

Our track record speaks for itself

Years Experience
0 +
Countries Served
0 +
Projects Completed​
0 +