Product Overview
The SC(B)13 is a three-phase cast-resin dry-type transformer. The listed technical range covers 30 to 2,500 kVA, with 6, 6.3 and 10 kV high-voltage options and a 0.4 kV low-voltage rating. The rating-specific loss schedule supports selection for the required distribution duty.
Construction and Features
- Three-phase cast-resin dry-type construction.
- Yyn0 or Dyn11 connection groups shown in the technical schedule.
- Model-specific no-load and load-loss data for the listed capacities.
- Applications described in the brochure include power networks, industrial facilities, urban infrastructure, ports and shopping centres; suitability depends on the project requirements.
Technical Parameters
| Parameter | Technical Data |
|---|---|
| Listed rated capacities | 30–2,500 kVA |
| Number of phases | Three-phase |
| High-voltage options shown | 6 kV, 6.3 kV and 10 kV |
| Low-voltage rating shown | 0.4 kV |
| Connection groups shown | Yyn0 or Dyn11 |
| Insulation system, enclosure and cooling | Confirm for the selected configuration |
SC(B)13 Loss Data
| Rated Power (kVA) | No-load Loss (W) | Load Loss (W) |
|---|---|---|
| 30 | 133 | 639 |
| 50 | 189 | 900 |
| 80 | 259 | 1242 |
| 100 | 280 | 1413 |
| 125 | 329 | 1665 |
| 160 | 378 | 1917 |
| 200 | 434 | 2277 |
| 250 | 504 | 2484 |
| 315 | 616 | 3123 |
| 400 | 686 | 3591 |
| 500 | 812 | 4392 |
| 630 | 910 | 5364 |
| 800 | 1064 | 6264 |
| 1000 | 1239 | 7317 |
| 1250 | 1463 | 8721 |
| 1600 | 1715 | 10557 |
| 2000 | 2135 | 13005 |
| 2500 | 2520 | 15453 |
The 1,000 kVA entry lists a no-load loss of 1,239 W and a load loss of 7,317 W.
Loss values follow the product catalogue schedule. Confirm the reference temperature, voltage configuration and guaranteed losses in the approved technical schedule before comparing series or placing an order.
Selection and Enquiries
Send the required rated capacity, primary and secondary voltages, frequency, connection, installation conditions, enclosure requirements, quantity and project location. Request the confirmed dimensions, weight, sound-level data, short-circuit impedance and scope of supply for the selected unit.
Installation and Maintenance
Installation, ventilation, fire-safety provisions and any hazardous-area requirements must be assessed for the selected design and site. Dry-type construction does not by itself establish an explosion-protection rating. Follow the manufacturer’s installation, inspection and maintenance instructions.